Не удалось загрузить сведения о доступности самовывоза
Generator Control Unit ESD5111 is a closed-loop control of the entire electronic design, it's instantaneous load changes quickly and with precision control in response to engine speed when connected to the match and the implementation of e-speed magnetic sensor signals can be Control of a wide range of engines.
It is designed to be highly reliable, the engine can withstand the surrounding area within the range of electromagnetic interference. In the design, installation and a simple pre-adjustment, including the transfer rate and adjustable idle for assistance or for multiple special-purpose machine input, as well as to prevent reverse battery voltage, the transient voltage pulse, the actuator short-circuit fault And the loss of power or speed sensor signal of the security protection
PERFORMANCE of ESD5111 Generator Speed Control Unit
Isochronous Operation/Steady State Stability
± 0.25% or better
Speed Range/Governor
1K-7.5K Hz continuous
Speed Drift with Temperature
± 1% Maximun
Idle Adjust CW
Min. 1200Hz. below set speed
Idle Adjust CCW
Min. 4100Hz. below set speed
Droop Range
1-5% regulation
Droop Adj. Max. (K-L Jumpered)
875Hz., ± 75Hz. per 1.0 A change
Droop Adj. Min. (K-L Jumpered)
15Hz., ± 6Hz. per 1.0 A change
Speed Trim Range
± 200Hz.
Remote Variable Speed Range
500 -7.5Hz. or all part thereof
Terminal Sensitivity
J: 100Hz., ± 15Hz/Volt @ 5.0 K Impedance
L: 735Hz., ± 60Hz/Volt @ 65 K Impedance
N: 148Hz., ± 10Hz/Volt @ 1Meg. Impedance
P: 10V DC Provide @ 20ma Max.
Speed Switch Adjustment Range
1000-10000Hz.
ENVIRONMENTAL
Ambient Operating Temperature Range
-40°c to +85°c
Relative Humidity
up to 95%
Storage Temperature
-55°c ~ 90°c
Shock
20-100HZ 500mm/Sec.
INPUT POWER
Provide
12 or 24V DC Battery Systems(Transient and Reverse Voltage Protected)
Polarity
Negative Ground(Case Isolated)
Power Consumption
50mA continuous plus actuator current
Maximum Actuator Current at 25
10Amps continuous
Speed Sensor Signal
0.5-120 Volts RMS
PHYSICAL
Weight
630g
Note: The performance parameters in the frequency when measuring 4000Hzv