Product Introduction
1. INTRODUCTIO
NSensing Input
Voltage:95~132VACor190~264VAC1 phase, jumper selectable
Frequency:50160 Hz, selectable
Output
Voltage:Max. 90 VDC @ 207 VAC
Current:Continuous 4A ,Intermittent 10A for 10 sec.
Resistance:Min.15 ohm
Voltage Regulation
<+ 1.5% ( with 4% engine governing )
Voltage Build-up:Residual voltage at AVR terminal> 5 VAC
Thermal Drift:0.05% per C change in AVR ambient
External Volts Adjustment:7% with 1K ohm 1 watt trimmer
Unit Power Dissipationt:Max.10 watt
Under Frequency Protection:Set point ,95% Hz
( UFRO ): Slope 170% down to 30 Hz
Soft Start Ramp Time:2 sec.
Dimensions:135mmL*100mmW*49mmH
Weight:243g t 2%
WIRING (Refer to wiring diagram)
1. ConnectF1, F2 to DC output port.
2. Connect the sensing port at 7, 8 (the factory setupis 220V, if 110V is required, please join 3, 4)
3. External voltage regulator is as Figure 4.
4. Connect a jumper from COM to the 50Hz terminal for 50Hz operation.
Note :
please install 5A 250V fuse at power input portas Figure 4