Applications Standard : for LSA 40 alternators. Adapted to the SHUNT and AREP excitation system
Main characteristics Voltage regulation +/- 0.5% at steady state and constant speed. Response time 500 ms Nominal excitation current : 3A Maximum excitation current 7A for 10 sec. Alimentation and detection 85 to 139 V (50/60Hz) Protection : Fuses embeded in resin